1 NO contact not potential-free 16A/250V AC, 230V LED lamps up to 200W, incandescent lamps 2300W*. Stand-by loss only 0.5 Watt. Contact switching in zero crossing to protect contacts and lamps. In particular, this extends the life of energy-saving lamps. State-of-the-art hybrid technology combines the advantages of wear-free electronic control with the high switching capacity of special relays. Control voltage 230V and additional galvanically isolated universal control voltage 8..230V UC. Very low switching noise. Times adjustable between 0.1 seconds and 40 hours. Functions F: RV = off-delay. AV = response delay. TI = Clock generator starting with pulse. TP = Timer starting with pause. IA = Pulse-controlled response delay. EW = switch-on wiper. AW = switch-off wiper. ARV = On-delay and off-delay. ON = Duration ON. OFF = Duration OFF. The LED under the upper rotary switch provides information about the contact position during the time lapse. It flashes as long as the make contact is open and lights up continuously as long as the make contact is closed. The time base T is set with the middle latching rotary switch T.