• Suitable for protecting the DC side of a photovoltaic system in accordance with EN 5154332 Approval in accordance with lowvoltage switchgear combinations IEC 614391:• 2011 and EN 614392:• 2011 Fuse holder for input and output (order 10 x 38 fuses separately) With loadbreak switch for safe disconnection of the string cables Switching capacity loadbreak switch:• DCPV1, IEC 609473 MPP tracker Number:• 1 Input length:• 3 Output length:• 3Connections for article 62 163 72 via M25 cable gland with 3 x 7 mm cable entry PUSH IN terminals 2.5 mm to 16 mm singlethreaded, multithreaded, with/without wire endConnections for article 62 163 73 WM4 C plug connector, compatible with cable type TV 2 Pfg1169/08.07/ EN 50618:• 2063 Arrester with signal contact Connection of the signal contact via cable glands (812 mm) max. conductor crosssection:• 1.5 mm Connection of the functional earth via cable glands (812 mm ) Conductor crosssection:• 1625 mmProtection class:• IP65 Current per maximum power point, max.:• 45 A Rated shorttime withstand current:• 56.25 A Rated DC voltage:• 1.000 V Leakage current In (8/20 s):• 20 kA Leakage current, max. (8/20 s):• 40 kA Lightning impulse current Iimp (10/350 s):• 6.25 kA Total leakage current Itotal (10/350 s):• 12.5 kA Total leakage current Itotal (8/20/20s):• 50 kA Shortcircuit strength ISCPV:• 11.000 A Voltage of the PV system, max. UCPV:• 1,100 V Ambient temperature:• 40 C to +45 C Everything installed in a fibreglassreinforced plastic housing