• overvoltage protection box suitable for protecting the DC side. Max. String voltage 1000 V MPP tracker Connections for article 62 163 80 and 62 163 82:• WM4 C plug connector, compatible with cable type TV 2 Pfg1169/08.07 / EN 50618:• 2071 Connection to the box is made in the stub, without DC switch Connection of the functional earth via cable glands (812 mm ) Conductor crosssection:• 16mm Connections for article 62 163 81 and 62 163 83:• Connection via cable glands (48 mm ) Conductor crosssection:• max. 16 mm Connection to the box is made in the stub, without DC switch Connection of the functional earth via cable glands (812 mm ) Conductor crosssection:• 16 mm In accordance with the standard, EN 5053911:• 2013+A1:• 2014 IEC 6164331:• 2018 Protection class:• IP65 and 67 Operating temperature:• 40 C to 85 C Leakage current In (8/20 s):• 20 kA Leakage current, max. (8/20 s):• 40 kA Requirement class:• Type I/IILightning impulse current Iimp (10/350 s):• 6.25 kA Total leakage current Itotal (10/350s):• 12.5 kA Total leakage current Itotal (8/20s):• 50 kA Shortcircuit resistance ISCPV:• 11 kA Voltage of the PV system, max. UCPV:• 1,100 V