Choose your country of delivery to see prices and products for your location.
Choose tax zone / country of delivery
• For monitoring exhaust gas routing and controlling gas supply in commercial kitchen facilities • KCU kitchen control unit as central control unit • DW air pressure monitor for monitoring exhaust gas flow (extractor fan) • Central shut-off device ZAE, fully assembled unit on a mounting plate for easy wall mounting, consisting of: - 1x ball valve with test connection RVS 12 - 1x thermally activated shut-off element (TAE) - 2x solenoid valves closed when de-energised in accordance with DIN EN 161Kitchen safety device type EMS for monitoring exhaust gas routing and controlling the gas supply in commercial kitchen facilities. Example of use: With central control unit, pressure switch, solenoid valve, pre-installed ball valve and integrated thermal shut-off device T (TAE) Function: The air pressure monitor determines whether there is sufficient flow in the exhaust air chimney. The flow status determined by the air pressure monitor is evaluated by the KCU kitchen control system and a central shut-off device is activated. As long as there is sufficient flow in the exhaust air chimney, the two solenoid valves of the central shut-off device remain open and liquid gas can flow to the consumer.