Choose your country of delivery to see prices and products for your location.
Choose tax zone / country of delivery
Only calibrated meters are permitted for electricity billing according to paragraph 25 of the German Calibration Act. Non-observance is an administrative offence according to paragraph 19. Maximum current 32A, stand-by loss only 0.4 Watt. Modular device for mounting on DIN-EN 60715 TH35 rail. 1 division unit = 18mm wide, 58mm deep. Accuracy class B (1%). With S0 interface. This AC meter measures the active energy on the basis of the current flowing between the input and the output. The self-consumption of only a maximum of 0.4 Watt active power is not measured and not displayed. 1 outer conductor with a current of up to 32A can be connected. The starting current is 2OmA. If a load of more than 50% is to be expected, a ventilation distance of 1/2 pitch unit from units mounted next to it must be maintained. If necessary, use the DS12 spacer. Two N-terminals for safe cross-wiring of several meters. The 7-segment LC display can be read twice within two weeks even without power supply. To do this, press the key. Below the display there is a key which is used to scroll through the menu according to the operating instructions. First, the backlighting switches on. Then the total active energy, the active energy of the resettable storage tank and the instantaneous values of active power, voltage and current can be displayed. The power draw is indicated by a bar flashing 1000 times per kWh in the display. Error message: In the event of a connection error, the display backlight flashes.