Type: Sauter maximum safety pressure lim. DSH 152-F001 81855164 NEW
Properties:
- Switching point adjustable
- Sealable
- Pressure sensor made of brass for non-aggressive media (DSL)
- Pressure sensor made of stainless steel for aggressive media (DSH)
- Locking type: On falling pressure (DSL) or on rising pressure (DSH)
- SIL 2 certified according to IEC 61508
- Approved for marine applications (GL and LR certified)
Technical data:
Electrical supply
- Max. Load as gold contact1): 400 mA, 24 V, 10 VA
- min. load as gold contact: 4 mA, 5 V
- max. load as silver contact: 10(4) VA - max. load as silver contact: 4 mA, 5 V - max. load as silver contact: 10(4) VA Max. load as silver contact: 10(4) A, 250 V~, 50 W, 250 V=
- Min. load as silver contact: 100 mA, 24 V
Characteristic pressure connection: G½" A
Ambient temperature: -20...70 °C
Construction:
- Enclosure: Transparent cover
- Enclosure material: Impact-resistant thermoplastic
- Cable plug: Standard plug with cable socket for cables with Ø 6...10 mm
Standards and directives
- Protection class2): IP65 (EN 60529)
- Protection class: I (IEC 60730)
- Test mark3): TÜV
DSL: SDBF ID: 0000006022
DSH: SDB ID: 0000006023
PED: 2014/68/EU, Cat. IV
Ship approval: Germanischer Lloyd (GL) Lloyds Register
CE conformity according to:
- EMC Directive 2014/30/EU: EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
- Low Voltage Directive 2014/35/EU: EN 60730-1, EN 60730-2-6
- PED 2014/68/EU: VdTÜV Leaflet Pressure 100, Cat. IV EN 12952-11, EN 12953-9
- Machinery Directive 2006/42/EC (according to Annex II, 1B): EN ISO 12100
SIL conformity according to SIL 2:
- Standards: IEC 61508 Parts 1-2 and 4-7
1) If the contact is subjected to a higher load than specified, the gold layer is destroyed. It is then only considered a silver contact and loses the properties of the gold contact
2) Depending on the mounting position, see mounting instructions. The units are not suitable for outdoor applications.
3) Certificates for download at www.certipedia.com
PDF