Analogue value transmitter KMA-F8-The analogue value transmitter is used for manual control value setting, e.g. for mixing dampers, valve positions, temperature values, etc. The module can be controlled by two operating modes, which are set using the three-stage switch (ON, OFF, AUTO) on the front panel. The switch position is signalled via the external control contact terminals B1 and B2. Switch position inchONinch. The control value can be set using the potentiometer on the front. The output signal 0 to 10 V is available at terminal Y. The actuating variable is switched through to the actuating variable output Y via terminal YR without being changed.-Connection with spring terminals (push-in) Setpoint device Manual operating level with feedback-LED brightness proportional to the actuating variable-Features-Input/operating voltage24 V AC/DC Input/current consumptionAC 30 mA Input/current consumptionDC 19 mA Input/voltage0 to 10 V DC Output/voltage0 to 10 V DC Display LEDred