Type: ZQD NEWWeather-compensated controllerWould you like to receive 20 Euro for your defective item?Send us back your defective item of the same type and we will return it to you,after we have received the item and after expiry of the right of withdrawal, transfer 20 Euro to your bank account.1. print out the return documents (click here), fill them in and enclose them with the return.2. create a return slip (click here), print it out, stick it on the DPD parcel and hand it in free of charge at your nearest DPD station. Technical data: 230V 50Hz short-circuit-proof mains transformer (do not swap when connecting L1 and N) IP 40 Mounting Optionally on the wall or in the switch cabinet. Inputs: Outdoor temperature: Weather controlled TAD with active measuring system KP10 ( 2.73V at 0°C change 10mV/K ) Flow temperature sensor: TVD ( immersion sensor ) or TAVD ( contact sensor ) with active measuring system KP10 ( 2.73V at 0°C change 10mV/K ) Room temperature sensor: TRD2 with active measuring system KP10 ( 2,73V at 0°C change 10mV/K ) Boiler-, boiler-, limit temperature sensor: each TVD ( immersion sensor ) with active measuring system KP10 ( 2,73V at 0°C change 10mV/K ) Outputs: Two-way NO for actuator ( 3 point control ) 5 ( 1,5 ) A 250V, overload protection 1 NO for each: Circulation, boiler and circulation pump each 5 ( 1,5 ) A 250V, overload protection normally open for boiler ( burner ) potential free, 5 ( 1,5 ) A 250V, overload protection