Type: Honeywell 1650206U IRD1010.1 AXIAL white
Infrared flame detector Flame sensor Flicker detector NEW The IRD 1010.1 device is used to monitor an oil flame
This flame monitoring device is connected to a Satronic automatic oil burner control unit. The monitoring function is based on the infrared flicker principle, i.e. only the infrared flicker light of the flame is detected. The constant light radiation from any glowing brick lining of the boiler, for example, has no influence. The IRD 1010.1 replaces the IRD 1010, 910, 911 and 911 vi types. When replacing the IRD 1010, care must be taken to ensure that a type-corresponding IRD 1010.1 (blue, red, white) is used (see pages 3 and 4). When replacing the IRD 910, 911 and 911 vi, ensure correct connection (see page 3). To replace the IRD 910, 911 and 911 vi with the IRD 1010.1, the sensor cable is also required. The IRD 1010.1 infrared flicker detector can be operated with the following control units: DKO 970, 972, 974, 976, 992, 996 DMO 976 DKW 974, 976 TF 801, 802, 804, TF 830, 832, 834, 836 TF 844, 874, 876, 974, 976 MMD 900, 900.1 TTO 872, 876 MMO 872, 876 TMO 720-4 Version: white AXIAL: PHOTOCELL FRONT
Operating voltage: 220 / 240 V (-15... +10%), 50 Hz (50 - 60 Hz) or 110/120 V (-15... +10%), 50 - 60 Hz (±5%)
Rated current consumption: approx. 4 mA Power consumption: 1 VA Ambient temperature: -20° C... +60° C Protection class: IP 41 Mounting position: any Weight: 40 g Use of the sensor: axial or radial depending on type Spectral range: 800 - 1100 nm (with daylight cut-off filter): Maximum 950 nm Frequency range: 15 Hz... 250 Hz (-12 dB) Sensitivity adjustment range: approx. 1 : 20 (26 dB) Switch-on delay: - (after applying the operating voltage) < 3.5 s - Response time < 0.1 s - Sign-off time < 1 s Climatic conditions: max. 95% at 30° C Climatic conditions: max. 95% at 30° C
Temperature range: - Operation -20° C... +60° C - Storage -20° C... +80° C Ice formation, exposure to water and condensation are not permitted Tested in accordance with Euro standards EN 230, as well as all applicable provisions and regulations
- Suitable for Abig: Nova 2014 AC, Nova 2014 BC - Ref. no. : 70210-011
- Suitable for Buderus BRE, TE 1.0/1.1 - Ref. no.: 5883617
- Suitable for elco: V-BL01.22/28/35, V-BL01.18/22D, V-BL1.20, V-BL1.24, V-BL1.28, V-BL1.30, V-BL1.35, E018.18/22L-Z, EK01.828/3SL-NH, EK018.2BL-NH (SH113), EK1B.3SL-NH (SH113), VB2.38-100
- Ref. no.: 13012678 replaces 13011127
- Suitable for MAN: RE 1LN/RE2
- Ref. no.: 95.95214-0048
- Axial white - Replaces IRD 910
- Manufacturer no.: 1650206
- the following items are also suitable for 20 005 40
Abig: Nova 2014 AC, Nova 2014 BC Ref. no.: 70210-011
Buderus: BRE Ref. no.: 5883617
MAN: RE 1LN/RE2, Axial White Replaces IRD 910, Axial White Ref. no.: 95.95214-0048
Intercal: BNR 10, BNR 100 Ref. no.: 88.70020-0300 20 005 47
Viessmann: Rotrix burner type IRD 1010
PDF