Area of application:- Heating systems with buffer cylinder and solar heating support - Control of underfloor and panel heating systemsRecommended area of application:- Up to 32.5 KW- 20 K to 1400 l/hTechnical data:- Connection producer: 1 1/2" AG flat-sealing- Connection consumer: 1" IG- Max. Pressure: 6 bar- Max. Operating temperature: 110°C- Insulation to EnEV: made of EPP- Centre distance: 125 mm- Pump: Wilo Para SC 25/6-433-temperature mixerThe 3-temperature mixer is used in conjunction with a buffer cylinder that can be heated by a solar thermal system, a solid fuel boiler or a conventional boiler.If the consumer only requires a low temperature level, e.g. for panel heating systems, the 3-temperature mixer initially draws the flow water from the centre storage tank area. Only when the temperature in this area is no longer sufficient is the water from the top, hot cylinder area used.By using two cylinder areas for two different flow temperatures, the energy in the buffer cylinder can be utilised more efficiently. The return temperatures are low and the temperature stratification in the buffer cylinder is maintained.