- Fixed setting for indoor installation in conjunction with a pre-stage regulator (58 004 28)- With safety shut-off valve OPSO (SAV) and additional safety diaphragm, this eliminates the need for the safety relief valve PRV and it is not necessary to discharge the excess pressure to the outside!- With thermal shut-off device TAEfor automatic shut-off of thegas flowif the temperature rises above 100°C- Inlet: DN 15 (1/2") IG- Outlet: DN 20 (3/4") IG- Outlet pressure: 50 mbar- Inlet pressure: 0.5 - 2.5 bar- Output: 12 kg/h- Conformity: EU type examination certificate DGR, GGVSafety(safety valve setting values for tanks usually 15.6 bar)Gas meter for propane systems:The supplier delivers the propane gas in the liquid phase and bills in kg for cylinders or in litres for tank systems. However, a gas meter records the gas phase and displays m3. In the case of several consumptionunits with one storage tank, all units must be equipped with one meter due to legal requirements, so that billing is based on the ratio of m3 consumed.For control purposes or in special cases, this ratio can be determined as follows (values depend on temperature and pressure):Density of the gas phase in kg/m3 : density of the liquid phase kg/l Example: 1.97 kg/m3 : 0.51 kg/l Result: 3.86 l/m3