- For underfloor temperature control with combined underfloor/radiator heating- Sensor element connection: clamp- Suitable sensor elements: FJVRTechnical data:- Max. operating pressure: 10 bar- Max. operating temperature: 120°C- Max. differential pressure: 1 bar- Material: Brass, matt nickel-platedThe FJVR return temperature regulator is an automatic proportional regulator for regulating the mediatemperature. FJVR consists of a thermostatic element and a valve body. The thermostat closes when the temperature rises. FJVR can be used, among other things, to limit the return temperature on radiators, as frost protection and, in particular, as a simple, cost-effective control for underfloor temperature control in a combined underfloor/radiator heating system. As the use of an FJVR for underfloortemperature control only affects the water volume and spread, but not the flow temperature, particular attention must be paid to the maximum permissible flowtemperature for the floor structure and the pipe materials used. The ambient temperature at the installation location should not exceed the temperature set on the sensor.