Logaplus heat pump package WLW196 iAR-5Swith
Logatherm WLW196-14 iARE, reversible air-to-water heat pumpfor
mono-energetic
operation, with heating-supported
solar thermal system and DHW preparation via
fresh water station.
-
---------------------------------------Included in the package:
- WLW196-14 iARE-
Installation package INPA WPL 6-14 AR-
Cover hood for INPA WPL 11-14 AR-
Condensate drain heating-
Heating circuit set HSM25 V3-
Temperature monitor AT 90 E-
Heating circuit module MM100-
WMS 1, Wall mounting set for 1 heating circuit-
Connection set AS HKV25, HS/HSM25-
Logafix expansion vessel BU-H 35 L- Logafix
expansion vessel BU-H 80 L- Logafix
cap valve MS 3/4" x 3/4"- Logafix cap valve MS
1" x 1"-
Buffer tank PNRZ1000.6 ES-B-
Pipe trace heating 3 m-
3x 3-way switching valves 28 mm incl.
motor-
Buderus Logalux FS20/2-
Boiler safety group 1", pressure gauge,
safety valve 1/2", with insulation-
Univers. Check valve, 25 bar,
1Ms, special d. up to 110 C-
Double nipple 1" x 1
"----------------------------------------Heat pump
Logatherm WLW196-14 iARE-
Max. heating capacity 14,37 kW at A2
Max. heat output 14.37 kW at A2/W35- Coefficient
of performance 4.04 at A2/W35 according to EN14825
and part load-
Reversible air/water heat pump for mono-energetic
operation-
Logatherm WLW196-14 iARE, consisting of
IDU-14 iE + ODU_W 14
(Indoor unit = IDU-iE=
InDoorUnit_WaterOutdoorunit
= ODU_W=
OutDoorUnit_Water)
- Water connection between indoor
and outdoor unit-
Fast and
easy installation-
Including screed drying function and active
cooling-
Up to 62 C (at A>-2) flow temperature
possible with the heat pump-
Easy operation via EMS-plus service unit
Logamatic HMC300 with clear text display-
1 unmixed heating circuit controllable.
For mixed
heating circuits, accessories are required- Indoor unit
(IDU-14 iE):
With EMS-plus Logamatic HMC300 control unit-
Front panel made of modern, shatterproof
titanium glass.
Colour black-
With integrated internet interface
(RJ45 socket)
- High-efficiency heating water pump Grund-fos
GEO 25/85 for heating water circulation between
indoor and outdoor unit-
With 9 kW electric booster heater- Pressure
gauge, filter ball valve, air vent,
safety valve-
Diaphragm expansion vessel 10 litre-
Hot water operation
possibleby means of external switching valve
(accessory)
-
Electrical connection:3-phase alternating current (AC), 3-phase alternating current (DC), 3-phase alternating current (AC).
Electrical connection:
3-phase alternating current 400 V, 50 Hz-
Water-side connection for heating:
G 1" AG-
Minimum volume flow: 2.92 m3/h-
DimensionsWidth:
485 mmHeight:
700 mmDepth:
350 mmNet weight:
32 kg-Outdoor unit
(ODU_W 14):
- Inverter-controlled compressor and fan operation-
Patented Smart Soft Defrost function for
maximumrunning
times- Easy transport and sturdy construction-
Patented Smart Soft Defrost function for
maximumrunning times
Easy transport and shockproof due to compact
design with EPP material Technical
data:
- Heating capacity +7/35 C: 5.
63 kW
(according to EN 14825, part load)
- Heating capacity +2/35 C: 7.
86 kW
(according to EN 14825, part load)
- Heating capacity -7/35 C: 13.02 kW
(according to EN 14825, nominal capacity)
- COP +7/35 C: 4,87
(according to EN 14825)
- COP +2/35 C: 4,04
(according to EN 14825
)
- COP -7/35 C: 2,55
(according to EN 14825)-
Cooling capacity +35/18 C: 11,92 kW
(according to EN 14511)-
EER at A35/W18: 3,28-
Cooling capacity +35/7 C: 10,17 kW
(according to EN 14511)
- EER at A35/W7: 2,91-
Nom. Air flow rate: 7300 sqm/h-
Outside air temperature min./max.
heating mode: -20/+45Cooling mode
: +15/+45-
Compressor: Twin Rotary-
Sound power level according to
ErP (EN 12102): 53 dB(A)-
Max.
sound power level in daytime mode (
EN 12102): 53 dB(A)-
Max. sound power level in nighttime mode (EN
12102): 53 dB(A)
Sound power level in
day mode (EN 12102): 64 dB(A)- Max. sound
power level in
reduced night mode
(silent mode, EN 12102): 58 dB(A)-
Sound pressure level at
1 m distance (EN 12102): 45 dB(A)-
Refrigerant quantity R 410 A:4.
0 kg-
Max. flow temperature: 62 C- Electricity: Twin Rotary
Max. flow temperature: 62 C-
Electrical connection:
3-phase alternating current 400 V, 50 Hz-
Max. power consumption: 7.2 kW
Power consumption: 7.2 kW-
Water side connectionHeating
: G 1" ET-
DimensionsWidth:
1122 mmHeight:
1695 mmDepth:
545 mmNet weight:
184 kg----------------------------------------
EU DIRECTIVE ON ENERGY EFFICIENCYClass
for seasonal space heating energy efficiency of the
combined system: A++Energy efficiency class range:
A+++ ->
G Seasonal space heating energy efficiency of
the combined system
(boiler): -
Seasonal space heating energy efficiency of the interconnected system
at average climatic conditions
(HP) 149 %---------------------------------------- INFORMATION
RELATINGTO
F-GAS REGULATION 517/2014Environmental
Notice
: Contains fluorinated greenhouse gasesRefrigerant type
: R410ATrefrigerant global warming potential
- GWP: 2088 kgCO2eqFill quantity refrigerant:
4 kgFill quantity refrigerant:
8.352 tCO2eqCooling
circuittype
: hermetically sealed-
Buderus item no.
7739613105
----------------------------------------The
initial start-up and the required
periodic maintenance must be
carried out by Buderus
customer service or a
specialist companyqualified
and certifiedby
Buderus for this product
!
This service is not included and
must be ordered separately!
-
We would like to point out that we
canonly provide a warranty for
those system parts
that you
havepurchased from us.
Please observe the
component lists and hydraulic suggestionsprovided by us
. The use of other components
may
result inmalfunctions or a
loss of efficiency.
-
---------------------------------------5 years Buderus system warranty
(prerequisite: handover of certificate including
warranty conditions - activation
by end customer - annual maintenance)
PDF