Measuring function Specific:
- RLOW measurement with 200 mA DC test current and automatic polarity reversal / PE resistance measurement under mains voltage (3-wire method)
- Insulation resistance with test voltage of 50 V - 1000 V DC / RISO ALL, autotest between all conductors (L-N, L-PE and N-PE), RISO pre-test, protects connected devices from test damage
- Loop (LOOP) and line impedance (LINE) with 20 A test current incl. short-circuit current/voltage drop calculation for precise measurement results. Short-circuit current/voltage drop calculation for precise measurement results
- Testing of various RCD types: general, selective, AC, A, F, B, B+, EV RCD, EV RCM (RDC-DD), MI RCD, PRCDs
- RCD testing with RCD auto, RCD t, RCD I and Uc measurement
- TRMS voltage and frequency measurement, Rotary field and varistor testing
- First fault leakage current in the IT network (ISFL)
- Testing of EV charging stations (EVSE Mode 3) (wallboxes)
- Specially customised Auto Sequences® for 1- and 3-phase wallboxes incl. functional testing/testing of the charging station. Function test/testing of the charging process via optional BENNING EV 3-2 measuring adapter (044169)
- Testing of EV RCD and 6 mA DC residual direct current monitoring devices (RDC-DD) in accordance with IEC 62955 with measurement of tripping time and tripping current
- Documentation via ready-made EVSE test protocols
Performance features:
- Individual tests and pre-programmed Auto Sequence® measurements for TN/TT networks and EV charging stations (wallboxes)
- Automatic tests at the touch of a button, Z Auto (U, Zln, Zlpe, Ipsc, Uc) and RCD Auto (RCD t, RCD I, Uc), Auto TN rcd (U, Zln, Zlpe, Rpe, ?U), Auto TN, -TT and AutoIT
- Voltage monitor for online monitoring of the test connections
- Powerful 4400 mAh Li-ion battery pack for long operating times (optionally expandable to 8800 mAh (044170))
- Large measured value memory on 8 GB SD card
- USB, RS 232 and wireless interface (Cordless-Link) for data transmission
- Display: 4.5" capacitive colour touchscreen
- Low-impedance measurement: 0.01 O - 2 kO / 7mA
- Insulation resistance: 10 kO - 1000 MO
- Line impedance (L-N/L): 0.01 O - 10 kO / 0.1% - 100%
- Loop impedance (L-PE): 0.01 O - 10 kO
- Short-circuit current: 0.01 A to 200 kA
- FI/RCD type: AC / A / F / B / B+ / EV-RCD / MI-RCD / EV-RCM
- Phase sequence test: right/left in three-phase networks
- Voltage: 1 V - 550 V
- Frequency: 14 Hz - 500 Hz
- Earthing resistance: 0.01O - 1999 O (via earthing set)
Application:
- Auto Sequence® installation tester for the efficient testing and documentation of electrical systems and EV charging stations (wallboxes) of charging mode 3, as well as safety tests on electrical systems in accordance with VDE 0100/0105 and IEC 60364 after installation, modification or as a regular periodic test
Innovative operating concept:
- Operation via 4.5" colour touchscreen and pushbutton, order manager for processing and managing test orders
- Creation of multi-layered system structures including planned measurements directly at the test location and on the PC
- Device administrator and user account management
- All measurement functions with help function and PASS/FAIL display via stored backup characteristics for LOOP/ LINE measurements
- Connection for barcode scanner to identify the measuring point
Measurement functions via optional accessories:
- Testing of 1-phase and 3-phase EV charging stations (wallboxes) incl. Function test/testing of the charging process via optional test adapter BENNING EV 3-2 (044169)
- Two methods for earth resistance measurement via optional earthing set (044113) (non-selective) and current clamp adapter BENNING CC 4-1/CC 4-2 (044166/044167) (selective)
- TRMS current, Power and harmonic distortion (THD) measurement via optional current clamps BENNING CC 4-1/CC 4-2 (044166/044167)
- TRMS load currents up to 300 A AC/DC via AC/DC current clamp adapter BENNING CC 3 (044038)
- Testing of 5-pin, 16 A CEE sockets via optional CEE measuring adapter BENNING TA 6 (044168)
- Illuminance measurement via optional BENNING luxmeter type B (044111)
- Scope of delivery:
- Padded carrying case
- BENNING PC-Win IT 130-200 protocol software via download link
- USB interface cable
- Commander test plug
- Universal 3-wire test lead
- Test probe crocodile clip set
- Rechargeable Li-ion battery pack (4400 mAh)
- Charger
- 8 GB SD card
- Calibration certificate
PDF