Resideo 02234U TF834.3 Replacement for 02204U TF834 burner control unit
Intended use
Combustion controller for controlling and monitoring single-stage forced-draught burners with or without oil preheaters up to 30 kg/h. Replacement for Honeywell 02204U TF 834.
When selecting this product, check that the full part number and the version specified in the product details match.
Technical data
- Honeywell TF 834.3 automatic burner control unit 02234U
- At a glance
- Operating voltage: 220–240 V (-15/+10 %), 40–60 Hz
- Back-up fuse: 10 A fast-acting or 6 A slow-blow
- Power consumption: approx. 5 VA
- Pre-flushing time: approx. 12 s
- Single-stage operation
- Undervoltage protection in accordance with EN 230
- The oil preheater is de-energised in the event of a fault shutdown
- Technical data
- Pre-ignition time: approx. 12 s
- Post-ignition time: approx. 20 s
- Delay for valve 2: approx. 20 s
- Waiting time after fault shutdown: approx. 60 s
- Flame sensor: MZ 770 S, IRD 1010 or UVD 970
- Sensor current during operation: at least 30 µA
- Weight including base: 0.25 kg
- Installation position: any
- Protection rating: IP44
- Ambient temperature: 0–60 °C
- Approval: EN 230
- Maximum output current: Class 3: 1.5 A · Class 4: 4 A · Class 5: 0.5 A · Class 6: 4 A · Class 7: 0.1 A · Class B: 0.5 A · total: 5 A.
Notes
- Safety time: 10 s
- Selection guidelines
PDF
Product safety information
Manufacturer information:
Resideo Pittway Sarl
Zone d'activite La Piece 6
Zürich
Rolle, Schweiz, 1180
[email protected] https://www.resideo.com/de/de/
| Item information |
Value |
| Shipping weight: |
0,22 kg
|
| Item weight: |
0,18 kg
|
| LaNr.: |
02234U |